Power Cable

Typical Structure and Parameter of ADSS

Some structures and characteristics of typical representative ADSS are shown in the below list, however, they do not represent the whole products of the company. If you have any requests, please contact local representative office or contact the company directly.

ADSS with grade A sheath (Parts)

Structure drawing

Order Type Model

ADSS-PE 24 M15.5/ A

ADSS-PE48 M17.7 / C

ADSS-PE72 M21.2 / D

Fiber count

24fiber 48fiber 72fiber

Size of tube

φ2.1mm φ2.6mm φ3.0mm

Cable diameter

φ13.4mm φ14.9mm φ16.4mm

Cable weight

139kg/km 172kg/km 209kg/km

RTS

38.8kN 44.3kN 56.6kN

Linear expansion coefficient

2.2×10-6/℃ 2.0×10-6/℃ 1.8×10-6/℃

Young’s modulus

16.5kN/mm2 17.5kN/mm2 18.6kN/mm2

ADSS with grade B sheath (parts)

Structure drawing

Order Type Model

ADSS-AT 24 M14 / A

ADSS-AT48M15.2 / C

ADSS-AT72 M21.2 / D

Fiber count

24fiber 48fiber 72fiber

Size of tube

φ2.1mm φ2.6mm φ3.0mm

Cable diameter

φ13.2mm φ14.3mm φ16.3mm

Cable weight

146kg/km 169kg/km 220kg/km

RTS

35kN 37.9kN 52.9kN

Linear expansion coefficient

4.5×10-6/℃ 4.8×10-6/℃ 3.6×10-6/℃

Young’s modulus

15.5kN/mm2 14.9kN/mm2 17.9kN/mm2

ADSS with grade B sheath (parts)

Structure drawing

Order Type Model

ADSS-AT144 M12.3 / D

Fiber count

144芯

Size of tube

φ3.0mm

Cable diameter

φ20.7mm

Cable weight

344kg/km

RTS

30.8kN

Linear expansion coefficient

3.5×10-6/℃

Young’s modulus

6.22kN/mm2

Ordering Inion

Type model explaining:

We could provide user structure design and type selection, if inion is provided as below:

Weather condition

Temperature (℃)

Wind speed(m/s)

Ice thick (mm)

Lowest temperature

Average temperature of year

Max. wind speed

Ice thickness

Highest temperature

Installation


Electric line condition

System voltage*

kv

Type model/diameter* of ground wire

mm
Length of * mm

Type model/diameter* of conductor

mm

Name height of pole/tower

m

Split conductor/split spacer(y/no)

mm

Representative span*

m

Initial sag of wire*

%

Max span*

m

Max sag of wire*

%

Main installation operation requirement to ADSS cable

Installation sag*

%

Max sag

%

Min distance above ground*

m

Main transmission requirement to ADSS cable

Fiber count*

Fiber type*

attenuation*

1310nm: dB/km; 1550nm: dB/km;

Chromatic

dispersion

1310nm: ps/nm.km; 1550nm: ps/nm.km

Note 1:In some case, detail inion of poles and towers and cross section drawing of line is needed.

Note 2:“*” represents inion must be provided.

Hardware and Fittings for ADSS

The drawings below are shown with no detail size. If you have any requests, please contact local representative office or contact the company directly.

Dead end clamp with double stranded

Dead end clamp with single stranded

Suspending clamp (single)

Suspending clamp(double)

Spiral vibration reducer Tangent clamp
corona-resistring Joint-box
Wire clamp for tower Wire clamp for pole